COM.SAR IT Cleaning

Particle count testing to ISO 14644-1 for data centers and server rooms

We test air cleanliness in data centers, server rooms and electrical and mechanical rooms using the procedure set out in ISO 14644-1. The usual target is ISO Class 8, which many server and storage manufacturers require for their equipment. Testing shows the baseline, verifies the result of a cleaning or serves as evidence when a new build is handed over. We record temperature and humidity at the same time. You can also order testing on its own, without cleaning.

Request testing
Illustration: magnified dust particles under a magnifying glass and a particle counter with measuring channels from 0.3 to 5 µm.
Illustration: particle counter with measuring channels

When particle count testing makes sense

  • Before cleaning: It shows the baseline and where contamination is highest.
  • After cleaning: A verification measurement at the same locations and in the same occupancy state confirms the result.
  • At the handover of a new build: as evidence for acceptance, for example after pre-commissioning cleaning.
  • Regularly under a maintenance contract: Comparing several dates shows whether dust ingress is changing, for example due to construction work, new supply air paths or more frequent access.
  • After construction work or dust ingress: to clarify whether and where cleaning is needed.
  • On its own, without a cleaning contract: for example as a check for your records or as a basis for deciding whether cleaning is needed.

ISO Class 8 limits

The values state the maximum permitted number of particles per cubic meter of air. Each value counts all particles at or above the stated size.

Maximum concentrations for ISO Class 8 under ISO 14644-1
Particle sizemaximum per m³ of air
≥ 0.5 µm3,520,000
≥ 1 µm832,000
≥ 5 µm29,300

For background, see our article ISO 14644-1 Class 8 in data centers.

How we test

  • Sampling locations to the standard: Their number follows from the floor area. A room of 50 m² needs at least 10 locations, a room of 100 m² at least 16 and a room of 1,000 m² at least 27.
  • Distribution: representative across the area, usually at working height. On request, we also test at agreed points, such as rack air inlets or inside a protected zone.
  • Instrument: an optical particle counter that is calibrated annually to ISO 21501-4. It counts particles in six size channels from 0.3 to 10 µm and also records temperature and humidity. We enclose the valid calibration certificate with the report.
  • Sample volume: at least 2 liters and one minute per location, as the standard requires.
  • Evaluation: Every single location must meet the limit.
  • Occupancy state: We record whether testing took place during operation or at rest. We usually test while IT equipment is live.

The test report

The report records sampling locations, times, conditions, values and observations, as well as temperature and humidity. We state the result in the form the standard specifies, for example “ISO Class 8; operational; 0.5 µm and 5 µm.” A floor plan shows where we tested. We agree in advance on what you need and who receives the documents.

If a location exceeds the limit

Then we look for the cause together with you, such as a leaking filter, unfiltered outside air or open penetrations to adjacent rooms. Cleaning the air paths, especially the raised floor, or changing the filters in the cooling units often helps. We then test again at the same locations.

What particle count testing does not cover

  • Corrosive gases: Particle count testing does not capture hydrogen sulfide or sulfur dioxide. These are assessed with separate corrosion measurements under ANSI/ISA-71.04.
  • Continuous monitoring: We test with handheld particle counters on agreed dates.
  • Cleanrooms: Our focus is IT infrastructure, not cleanrooms. Cleanroom qualification, for example in the pharmaceutical or semiconductor industry, is the job of specialized testing bodies.

How testing works

  1. Agree on target and test plan: rooms, sampling locations, occupancy state, date.
  2. On-site testing, coordinated with your site contacts, usually while IT equipment is live.
  3. Report with values, assessment and notes.
  4. If needed, cleaning and a verification measurement at the same locations.

GOOD TO KNOW

Particle count testing: your questions

Discuss your requirements
The room looks clean. Do we still need testing?

Visual checks reveal deposits on surfaces. You cannot see how many particles are suspended in the air. Testing makes this visible and comparable.

Is ISO Class 8 mandatory?

Not by law. However, many server and storage manufacturers specify it in their environmental specifications, and the engineering society ASHRAE recommends it for data centers.

How long does testing take?

That depends on the number of sampling locations. The counter samples for at least one minute per location, plus time for moving between locations and for documentation.

Can you test while IT equipment is live?

Yes, we usually test while IT equipment is live. Access, sampling locations and procedure are agreed with your site contacts.

Can I order testing without cleaning?

Yes. You can order particle count testing on its own, for example as a check for your records. If the results show a need for action, we discuss the next steps with you.

More on this topic

Assessing dust in IT: quantity, type and affected areas · Air filtration or environmental monitoring: what does a server room need?

LET’S UNDERSTAND YOUR REQUIREMENTS

Let’s discuss
your IT cleaning.

Request a free consultation